Sinorix NXN features the latest generation of inert gas extinguishing technology. It is based on the three natural extinguishing agents, Argon, Nitrogen and Carbon dioxide. In pure form or mixed compounds, these natural extinguishing agents provide outstanding properties to combat a wide variety of fire hazards without harming the environment.
Their respective properties give Sinorix NXN great flexibility when designing the appropriate fire safety concept.
Sinorix extinguishing solutions follow the principle of inertization. When released, the gas displaces the oxygen in the flooding area and thus suppresses the fire within seconds. Fires are extinguished without incurring collateral damage and they do not leave behind any residue for clean up or disposal.
The Sinorix extinguishing agents are excellent for fire classes A, B, C, D and E.
By applying ADVtechnology the number of different components has been significantly reduced. This facilitates handling and leaves no room for confusion, as only one type of each component is used. At the same time, the actuators have been reduced in size, making them lighter and easier to handle during installation and maintenance.
Due to an adaptation in the mechanical design of the cylinder valve, the gas cylinder can open with a lower pneumatic pressure. This means that only one type of manifold, control hose, discharge hose and pneumatic actuator is needed – covering the full pressure range (8 – 360 bar).
Furthermore, this new cylinder valve can accommodate either an electric or a pneumatic actuator, so only one type of valve body is needed.
The check valve, pressure regulator, manifolds and connectors are all designed and equipped with the O-ring sealing mechanism. With a few twists of the wrist, and minimal force, all components are assembled by hand without needing special mechanical tools or additional sealants, such as hemp string or teflon tape.
Sinorix CDT – Constant Discharge Technology
Sinorix Constant Discharge Technology (CDT) is a technology where the cylinder valve releases the extinguishing agent at a constant mass flow.
But why is this important?
Conventional extinguishing systems are called unregulated, as they do not regulate the flow rate at which the extinguishing agent is released. This means that there is a huge pressure peak at the start of discharge, requiring large overpressure flaps.
In addition to overpressure, unregulated systems also generate a lot of noise during discharge. The resulting vibrations can severely impair the operation of hard disks or other sensitive equipment, for example in server rooms and data centers.
Sinorix CDT eliminates this pressure peak, resulting in lower noise levels and allowing the size of the overpressure flaps to be reduced by up to 70%.
In combination with Sinorix CDT, the Sinorix silent nozzle forms an unbeatable combination for protecting sensitive hard disks.
Its ingenious design further reduces the noise level during discharge of the extinguishing agent.
System Highlights
Advanced solutions for one of the world's most pivotal sectors, powering economi...
View MoreATP is at the forefront of the mining industry, addressing a unique set of chall...
View MoreWith depth of expertise, ATP delivers specialised solutions tailored for this va...
View MoreIts imperative correctional facilities are safeguarded from potential threats li...
View MoreComprehensive solutions for military precision, ensuring military personnel, equ...
View MoreAddress intrinsic risks and employ comprehensive solutions tailored for marine a...
View MoreATP embraces its role in fortifying the renewables sector in an era gravitating ...
View MoreRecognising inherent challenges, ATP has curated a suite of systems designed to ...
View More